Your benefits at a glance:- Custom leaf width and height
- Complies with EN 12101-2
- Variable opening and drive systems for daily ventilation and deaeration; combinations with CO2 or 24V type
- Ideally complements CI-System glass architecture M and glass architecture KWS 60
- Pefectly suited for retrofitting as it can be integrated with other systems
For more details on CI System glass architecture KWS 60 and CI System glass architecture M look here. Aw values depend on the individual application and can be quoted for your building project on request.
CI System smoke lift M
composition of flap: variable installation with angles of inclination between 30° and 60°

| |
glazing |
|
frame |
fittings |
| materials |
insulated glass max. geom. opening 2,0 m² |
PC-glazing max. geom. opening 3,5 m² |
aluminium with integrated screw duct |
aluminium/ stainless steel |
| fall-trough-proof during mounting as per German BG standard |
|
yes |
|
|
| hail-proof as per EMPA-norm |
|
yes |
|
|
| construction material classification |
A1 |
B2 (B1 on request) |
A1 |
A1 |
| physics |
Ug-value = 1,1 - 3,0 W/(m²K) |
Ug-value = 1,8 - 2,4 W/(m²K) |
|
|
composition of integrated frame

| function |
ideal connection to mullion and transm systems and light panel systems |
| material |
aluminium |
| construction material classification |
A1 |

The CI-system combination flap M
SHEV and natural ventilation for roof or façade in a variable system designed in a compact daylight element with real glazing and best-of-breed thermal insulation. With the CI-system combination flap M LAMILUX launches an extremely compact and high-quality manufactured flap system that besides its excellent energy values already today complies with tomorrow’s European standards. After a two year introduction phase the DIN EN 14351-1 will be effected from February 2009 onwards. By this the compulsory CE-marking for roof windows, windows and exterior doors will be implemented.

Our development - your advantages:- rain proof ventilation technology with integrated SHEV-operation in one flap system
- conformity with the European standard EN 12101-2 for SHEVs
- all-purpose integrated combination frame (IKF)
- possible integration into almost all profile-systems (roof/façade) with inclination from 0 to 90 degrees
- large choice of glazing variants: heat insulated glazing (thermal transmittance value 1,7 to 0,6), combined solar and heat protection glazing, sound proof glass
Approved quality:
The CI-system combination flap M has passed extensive numbers of tests such as - resistance to wind load (class C4/B5 EN 12210)
- resistance to driving rain (class E 1200 EN 12208)
- heat protection (thermal transmittance Ug value 1,7 to 0,6 W/[m2K] EN 673)
- total energy admission (g from 18 to 78 percent)
- air permeability (class 4 EN 12207)
- grade of light transmission (Lt from 19 to 82 percent)
- noise control (EN ISO 140-3 up to 45 dB)
Many European countries have special rules for stair wells. In most cases builders are required to fit electrically controlled, mains independent, smoke evacuation systems. For this purpose LAMILUX supplies smoke and heat ventilation systems custom-built for stair wells, although they can also be fitted in any type of building.
Connective lines for motors - wire cross sections
| number of motors |
max. length of wire in metre |
|
(double cross section) |
| |
3 x 1,5 mm² |
3 x 2,5 mm² |
5 x 2,5 mm² |
| 1 |
100 |
170 |
300 |
| 2 |
50 |
85 |
150 |
Your benefits at a glance:- Battery powered
- Electrically controlled with ventilation facility
- Supplied in kit form with all required motors, assembly instructions and connection plans
- Simple fitting by electrician
- Suitable for SHEV systems in roofs and on façades
The LAMILUX Standard Set comprises:- Electric motor 500 mm stroke, 24 V, switch-off under load
- Control unit for a maximum of two motors with control connectors for SHEVS and ventilation buttons, and various peripherals such as smoke alarms, thermal alarms or wind and rain sensors
- Two SHEVS buttons with visual display, surface mounted
- Flush mounted ventilation button for 55er back box
|