CI System Smoke lift / Smoke lift DH - versatile, economical and tested to EN 12101-2

Product description

The basis for CI System Smoke Lift is formed by our CI System Rooflight Dome and the CI System Night Flap with heat-insulated sandwich panels, plus the respective system required to control the SHEV function.

The benefits at a glance:

  • Upper section is not damaged when triggered during testing or due to false alarms; does not hit against the roof
  • Complies with DIN 18234 without the need for extra work or expense
  • Fitted with thermally activated release as standard
  • Maintenance-friendly, as the thermally activated release on individual devices remains intact in the event of remote triggering

Function variants

  • SHEV function optionally either open-only or open/close mode: the optional close function is used for simple, pneumatic closing after a functional test or inadvertent triggering via the alarm device. Advantage: there is no longer a need to spend time going onto the roof to close domes. This means that you can conveniently test the CI System Smoke Lift SHEV function at short intervals using the alarm device.
  • Remote triggering optionally pneumatic and / or electric
  • Functional test in open/close units using either CO2 or compressed air
  • Ventilation function either electric or pneumatic – 30 cm / 50 cm upstroke

Glazing types

MaterialsCompositeImpact-resistant compositeGF-UP*
Fall-through protection when installed as per BG guidelinesNoYesYes
Certified hailstorm protection as per Swiss EMPA standardNoYesYes
Building material classB2B1B2**

 

* Also available as a night flap with heat-insulated sandwich panels
** Also available as a "hard roofing" as per DIN 4102-7

Test parameters as defined by DIN EN 12101-2 and test results

 Flow coefficient Cv
 Effective aerodynamic opening surface Aw
between 0.60 & 0.75
between 0.6 m² and 3.38 m²
 Functional reliabilityRE 50/1000
+ 10,000 ventilation function openings
 Snow loadSL 500 - 2400
 Low ambient temperatureT(-05) T(-10) T(-15)
 Wind loadWL 1500
 Heat resistanceB300

Upstand

  • Upstand geometry aerodynamically optimised to ensure an effective flow of smoke
  • Upstand for good smoke extraction values without a corner spoiler
  • Steep upstand for enhanced smoke extraction values in combination with corner spoilers
  • Ideal structural mount
Design for 30, 40 und 50 cm upstands
MaterialsGRPSteel plateAluminium
Building material classB2A1A1
Compliance with DIN 18234 possible without additional measures such as gravel fillYesYesNo

Sizes and values

Aw values (m²)
Sloped up stand

Aw values (m²)
Steep up stand

with spoiler

Order size (cm)  

CO224V / 48V230VCO224V / 48 V230V
100/1000,600,60-0,750,710,75
100/1500,900,90-1,131,081,13
100/2001,301,24-1,501,441,50
100/2401,561,51-1,801,731,80
100/2501,631,58-1,881,801,88
100/3001,951,83-2,252,072,25
120/120 0,940,880,941,081,021,08
120/1501,171,121,171,351,301,35
120/1801,401,361,401,621,561,62
120/2401,871,871,872,162,102,16
120/3002,342,232,342,702,562,70
125/1251,020,971,021,171,111,17
125/2502,032,032,032,342,282,34
150/1501,461,421,461,691,621,69
150/1801,761,731,762,031,972,03
150/2001,951,951,952,252,192,25
150/2102,052,052,052,362,302,36
150/2402,342,342,342,702,632,70
150/2502,442,442,442,812,742,81
150/3002,932,842,933,383,203,38
180/1802,112,11-2,432,37-
180/2402,812,81-3,243,15-
180/2502,932,93-3,383,33-
180/3003,51--4,05--
200/2002,602,60-3,002,92-