Smoke and heat exhaust ventilation units (SHEV units) are essential components in any fire-protection concept. These life-saving, asset-protecting systems are compulsory requirements for “preventive fire protection”. We provide for a whole range of requirements, tailored to your project's needs: 
Open-only, open/ close, pneumatic, 24V, 48V, 230V; certified to EN 12101-2, SHEV designed and dimensioned in accordance with DIN 18232-2, regional building regulations and industrial construction guidelines – for rooflight domes, opaque flaps, individual flaps, continuous rooflights, glass roof constructions, staircases, Elevator shaft smoke extraction and wall glazing.

PRODUCT DESCRIPTION

ROOFLIGHT DOME NSHEV UNIT TO EN 12101-2


The basis for the CI System Smoke Lift F100  is our CI System Rooflight Dome F100 and the CI System Opaque Rooflight F100 with thermal insulated sandwich panels, plus the system required to control the SHEV function.

FUNCTION VARIANTS

  • SHEV function either open-only or open/ close mode: The optional close function is used for simple, pneumatic closing after a functional test or inadvertent triggering via the alarm device. Advantage: There is no longer a need to spend time going onto the roof to close domes. This means that you can conveniently test the CI System Smoke Lift SHEV function at short intervals using the alarm device.
  • Remote release pneumatic and/or electric
  • Functional test for open/ close units, either CO2 or compressed air
  • Ventilation function either electric or pneumatic – 30cm / 50cm stroke

GLAZING TYPES

MaterialsCompositeImpact-resistant compositeGRP*
Fall-through protection when installed as per BG guidelinesnoyesyes
Certified hailstorm protection as per Swiss EMPA standardnoyesyes
Building material class EN 13501)E-d0B-s1, d0E-d0**

* also available as an opaque flap with thermal insulated sandwich panels
** also available as “hard roofing” in accordance with DIN 4102-7

TEST PARAMETERS ACCORDING TO DIN EN 12101-2 AND TEST RESULTS

Our NSHEVs reliably open into the SHEV position in less than 60 seconds...

 

 ...and ensure a high smoke discharge volumeCv from 0.60 to 0.75
Aw from 0.6 m² to 3.38 m²
 ...after endurance test (1,000 times in SHEV position and 10,000 times in ventilation position)RE 50/1000 + 10.000 ventilation opening activations
 ...under snow loadSL 500 - 2400
 ...down to indoor temperature of -15 °CT(-15)
 ...after exposure to wind suction (up to 150 kg/m²)WL 1500
 ...when exposed to fireB300

UPSTAND

  • Aerodynamically optimised upstand geometry to ensure effective smoke flow
  • Upstand for good smoke extraction values without corner spoilers
  • Steep upstand for enhanced smoke extraction values in combination with corner spoilers
  • Ideal structural connection – Click here for more information
Upstand heights 30, 40 and 50 cm   
Materials GRPSteel sheetAluminium
Building material class (EN 13501)E-d0A1A1
Compliance with DIN 18234 possible without additional measures such as gravel fillyesyesno

DIN 18234 – EASILY ACHIEVED WITH LAMILUX

SIZES AND VALUES

ROOFLIGHT DOME NSHEV UNIT TO EN 12101-2


 Aw-values (m²)
Inclined upstand
 Aw-values (m²)
Steep upstand with spoiler
 

Order size (cm)  

CO224V /48V230VCO224V / 48 V230V
100/1000.600.60-0.750.710.75
100/1500.900.90-1.131.081.13
100/2001.301.24-1.501.441.50
100/2401.561.51-1.801.731.80
100/2501.631.58-1.881.801.88
100/3001.951.83-2.252.072.25
120/120 0.940.880.941.081.021.08
120/1501.171.121.171.351.301.35
120/1801.401.361.401.621.561.62
120/2401.871.871.872.162.102.16
120/3002.342.232.342.702.562.70
125/1251.020.971.021.171.111.17
125/2502.032.032.032.342.282.34
140/1401,251,22-1,431,41-
150/1501.461.421.461.691.621.69
150/1801.761.731.762.031.972.03
150/2001.951.951.952.252.192.25
150/2102.052.052.052.362.302.36
150/2402.342.342.342.702.632.70
150/2502.442.442.442.812.742.81
150/3002.932.842.933.383.203.38
180/1802.112.11-2.432.37-
180/2402.812.81-3.243.15-
180/2502.932.93-3.383.33-
180/3003.513.40-4.053.89-
200/2002.602.60-3.002.92-